Description
CCC FAN-10-2
Technical Specifications
- Product Type: Rack cooling fan unit
- Power Supply: 24 VDC
- Motor Type: Brushless DC motor
- Speed Monitoring: Built-in tachometer speed feedback
- Protection Function: Locked rotor protection
- Protection Rating: IP20
- Operating Temperature: -10 °C to +60 °C
- Mounting Method: Rack slot mounting
Functional Features
- Forced air cooling for CCC compressor control rack internal electronic modules.
- Built-in tachometer outputs real-time fan speed feedback signal to rack monitoring circuit.
- Locked rotor protection stops motor operation when fan blade is blocked.
- Fan fault signal is sent to CCC controller for fan failure alarm.
- Brushless DC motor reduces noise and extends service life.
- Integrated mounting frame enables quick installation and replacement.
- Overcurrent and reverse polarity protection for fan power circuit.
- Low vibration mechanical structure adapts to compressor cabinet environment.
- LED indicator displays fan running and fault status.
- Supports redundant fan configuration for high availability compressor control rack.
Application Scenarios
- CCC centrifugal compressor control rack thermal management
- Gas pipeline compressor control cabinet cooling
- Petrochemical plant compressor safety control rack cooling
- Refinery turbomachinery control system heat dissipation
- Power plant gas turbine auxiliary control rack cooling
Material Composition
- Fan frame: Reinforced plastic frame
- Fan blade: Fiberglass reinforced plastic impeller
- Motor housing: Aluminum alloy motor shell
- Motor components: Brushless DC motor coil and permanent magnet rotor
- Monitoring PCB: FR4 printed circuit board with speed detection circuit
- Terminal block: Copper alloy screw terminals for power and signal wiring
Structural Characteristics
- Integrated modular fan assembly matching CCC rack slot dimension.
- Axial fan blade mounted on brushless DC motor.
- Rear monitoring PCB collects fan speed signal and generates fault alarm signal.
- Standard mounting holes for fast installation inside rack.
- Airflow direction is designed to pass through heat generating electronic modules.
Working Principle When 24VDC power supplies the fan motor, brushless motor drives fan blade rotation to generate continuous airflow through rack modules. Tachometer sensor detects real-time rotation speed and sends speed feedback signal to CCC control system. When fan blade is blocked or motor fails, speed feedback signal deviates from normal range. The monitoring circuit triggers fan fault alarm and sends fault signal to compressor controller.
Installation Requirements
- Install FAN-10-2 assembly into designated fan slot of CCC rack.
- Confirm airflow direction matches rack thermal design requirement.
- Use correct wire gauge for 24VDC power wiring.
- Complete protective earth connection for fan frame.
- Verify speed feedback signal wiring to controller.
- Perform fan operation test after installation.
- Clear air inlet and outlet from dust obstruction.
Usage Notes
- Cut off power supply before removing fan assembly.
- Keep air inlet and outlet free of dust accumulation.
- Check fan vibration and noise periodically during long term operation.
- Replace fan assembly immediately when speed fault alarm appears.
- Do not block fan airflow during system operation.
- Avoid exposing fan assembly to oil mist and corrosive gas.