Description
Honeywell C7061F2001
Technical Specifications
- Brand: Honeywell
- Model: C7061F2001
- Product Type: Explosion-proof dynamic self-check ultraviolet flame detector
- Detection Method: Ultraviolet radiation sensing
- Compatible Amplifier: R7861
- Compatible Controls: Honeywell 7800 series burner controls
- Mounting Connection: 1 inch NPT pipe union
- Electrical Rating: 120 Vac
- Frequency: 50 Hz and 60 Hz
- Ambient Temperature Range: -40°F to +175°F, approximately -40°C to +79°C
- Enclosure Rating: Explosion-proof housing for hazardous locations
- Weight: Approximately 14.5 lb or 6.6 kg
- Leadwire Length: Approximately 2.4 m or 96 in
- Quartz Viewing Window Pressure Rating: 100 psi or 690 kPa
Functional Features
- Detects ultraviolet radiation from gas, oil, and other fuel flames.
- Provides dynamic self-check through an internal oscillating shutter.
- Designed for hazardous or explosion-risk environments.
- Uses a robust explosion-proof housing to reduce ignition risk in classified areas.
- Supports continuous flame monitoring in demanding combustion systems.
- Allows field replacement of the UV sensing tube and viewing window.
- Compatible with R7861 amplifier and 7800 series burner controls.
- Supports parallel detector installation where flame sighting is difficult.
- Provides improved mechanical protection compared with standard NEMA 4 detectors.
Application Scenarios
- Hazardous location burner applications.
- Gas-fired and oil-fired industrial burners in classified areas.
- Petrochemical, chemical, and refinery combustion systems.
- Process heaters and boilers requiring explosion-proof flame detection.
- Legacy Honeywell 7800 series burner control systems.
- Sites where C7061A detectors do not meet area classification requirements.
Performance Parameters
- Ultraviolet sensing tube rated down to -40°F or -40°C.
- Quartz viewing window pressure rating is 100 psi or 690 kPa.
- Explosion-proof housing suitable for hazardous locations; exact certification markings should be confirmed on the product nameplate.
- Flame signal evaluation depends on the R7861 amplifier and associated burner control.
- Exact response time, hazardous area classification, temperature class, and electrical connection details should be verified from the physical unit and official Honeywell documentation.
Material Composition
- Heavy-duty explosion-proof housing.
- Quartz viewing window rated for higher pressure.
- Ultraviolet sensing tube.
- Oscillating shutter assembly.
- Internal gaskets and sealing components.
- Color-coded electrical leadwires.
- Metal mounting hardware and pipe union.
Structural Characteristics
- Explosion-proof two-piece or heavy-duty housing design.
- Larger and heavier than the C7061A series due to the explosion-proof construction.
- 1 inch NPT pipe union for secure mounting to a sight pipe.
- Front optical window designed for higher pressure resistance.
- Internal shutter mechanism for dynamic self-check.
- Alignment features to ensure correct shutter operation.
- Designed to maintain flame-path integrity in hazardous environments.
Working Principle
The C7061F2001 operates like other C7061 detectors by sensing ultraviolet radiation from a flame. The internal shutter periodically blocks UV radiation to verify that the sensing tube is still functional. This dynamic self-check helps prevent undetected failures. The detector sends the flame signal to the R7861 amplifier, which determines whether a valid flame is present. The explosion-proof housing ensures that internal electrical components are isolated from potentially explosive atmospheres.
Installation Requirements
- Confirm that the hazardous area classification matches the detector certification.
- Install using the 1 inch NPT pipe union and a suitable sight pipe.
- Maintain a clear optical path to the flame.
- Verify that the supply voltage matches the 120 Vac rating of the C7061F2001.
- Use approved wiring methods for hazardous locations.
- Ensure all housing seals, gaskets, and threaded connections are properly tightened.
- Do not modify the housing, window, or flame path components.
- Perform flame signal verification after installation.
- Follow plant safety, electrical, and hazardous area installation requirements.
Precautions for Use
- The C7061F2001 must only be used where its explosion-proof rating is applicable and approved.
- Do not substitute a C7061A detector where an explosion-proof detector is required.
- Keep the viewing window clean and inspect it regularly.
- Do not operate with damaged housing, seals, or connectors.
- Replace only with approved UV tubes, windows, and gaskets.
- Verify compatibility with the R7861 amplifier and burner control before commissioning.
- Store spare detectors in dry, clean, and protected conditions.
- Refer to official Honeywell documentation for certification limits, wiring, and maintenance procedures.