Description
Honeywell FC-PSU-UNI2450
Technical Specifications
- Input Voltage Range: 85VAC to 264VAC single phase
- Input Frequency: 47Hz to 63Hz
- Output Rated Voltage: 24VDC
- Maximum Output Power: 450W
- Maximum Output Current: 18.75A
- Working Ambient Temperature: -20°C to +70°C
- Storage Temperature: -40°C to +85°C
- Relative Humidity: 5% to 90% RH non-condensing
- Isolation Voltage: 2000VAC between primary and secondary circuit
- Mounting: Hot-swappable plug-in on Safety Manager rack
- Certification: TÜV SIL2, UL, C-UL, CE, RoHS
Functional Features It supports hot swap operation during SIS system running. It works in parallel redundant mode with same model power modules. It includes overvoltage, overcurrent, short circuit and overtemperature hardware protection. It continuously monitors input power, output voltage and internal temperature. It transmits fault diagnostic information to Safety Manager backplane bus. It has independent LED indicators for power, fault and redundancy status. It limits inrush current during power-up sequence. It stabilizes output under wide input voltage fluctuation.
Application Scenarios Indoor clean control room SIS ESD rack power supply Chemical plant non-corrosive workshop safety interlock cabinet Power plant boiler safety shutdown system power Land-based natural gas processing plant SIS cabinet Refinery central control room safety system power backup Safety Manager standard spare module replacement
Performance Parameters
- Output Voltage Regulation Accuracy: ±0.5% full load
- Ripple Noise: Less than 120mV peak to peak
- Mean Time Between Failures: 830000 hours
- Redundancy Switchover Time: Less than 8ms
- EMC Surge Withstand: 2kV line to ground
- Power Hold-up Time: 20ms at rated load
Material Composition FR4 flame retardant bare PCB board High speed switching power semiconductor devices Isolation transformer Precision current sampling resistors Temperature detection thermistor TVS surge protection components ABS flame retardant front panel Tri-color LED status indicators Metal locking clip and gold finger connector
Structural Features Standard plug-in rack module dimension compatible with Safety Manager rack. Front panel equipped with power, fault and redundancy LED indicators. Side anti-reverse insertion key notch. Rear gold finger connector mates with rack power backplane. Internal layout separates high voltage input circuit zone and low voltage output circuit zone. Passive air cooling channel for heat dissipation. Locking buckle fixes module to resist cabinet vibration.
Working Principle AC input signal passes EMI filter and rectifier bridge to convert into high voltage DC. PWM switching circuit converts high voltage DC into isolated stable 24VDC output. Feedback sampling circuit dynamically adjusts PWM signal to maintain constant output voltage. The built-in monitoring circuit tracks voltage, current and temperature signals. When fault condition triggers protection threshold, the module cuts off output and sends fault alarm to SIS controller. Redundant modules share load evenly and take over full load if one unit fails.
Installation Requirements Cut off rack main power before inserting module. Align anti-misalignment notch and insert into empty rack slot, lock buckle. Connect AC input cable to front panel terminal block. Configure redundant power group in Safety Manager engineering software. Power on rack and verify LED status and output voltage value. Separate AC power wiring from analog signal wiring. Keep air circulation space around module.
Usage Notes This standard version cannot be used in offshore, salt fog or corrosive gas environment. Redundant pair must use FC-PSU-UNI2450 same model modules. Static protection must be applied during replacement. Do not exceed rated 450W output power. Do not apply AC voltage to 24VDC output terminals. Keep cabinet clean and dry to avoid PCB corrosion.