ABB CDS200918R0001

Product Brief:​ This is an add-on capacitor module or option board for ABB industrial drives that increases the DC-link energy storage, allowing the drive to ride through short-duration voltage sags (typically 100–200 ms at half-load) without tripping.

Category: SKU: ABB CDS200918R0001

Description

ABB CDS200918R0001

  • Technical Specifications
    • Compatible Drives: ABB ACS800, ACS880 series (frame size dependent)
    • Ride-Through Extension: Adds approx. 100–500 ms depending on load & frame
    • Capacitor Type: Metallized polypropylene film / electrolytic bank (drive-size dependent)
    • Installation Location: Inside drive enclosure or separate wall-mount cabinet
    • Cooling: Forced air or natural convection per enclosure rating
    • Max Ambient: +40 °C (derating above)
    • Standards: IEC 61800-5-1, UL, CE
  • Functional Features:
    • Automatic charging/discharging management by drive control board
    • No external control wiring required — detected automatically by drive firmware
    • Extends process continuity during brief utility disturbances
  • Application Scenarios:
    • Critical conveyor/crane drives sensitive to momentary line dips
    • Paper machine section drives requiring coordinated ride-through
    • Pump/compressor applications where nuisance trips are costly
  • Material & Structure:
    • Capacitor cans: Aluminum housed with epoxy sealed terminals
    • Mounting bracket / DIN rail clip (internal) or separate floor-standing cabinet
  • Working Principle:

    During normal operation the capacitors are charged to DC-link voltage. When AC input sags, the inverter continues drawing energy from the DC link; the added capacitance slows the DC-link voltage decay, keeping it above the undervoltage trip threshold for the extended period.

  • Installation Requirements:
    • Must be installed by qualified personnel with drive de-energized and wait ≥5 min for residual charge dissipation
    • Verify drive firmware supports CDS option before ordering
    • Follow torque specs for busbar connections
  • Precautions:
    • Capacitors store lethal voltage after power-off — always discharge before handling
    • Do NOT install if drive frame/software does not explicitly list CDS compatibility
    • Ensure proper ventilation around capacitor bank