Emerson 1C31150G01

Product Introduction: This relay output terminal base matches Ovation digital output I/O card. It receives digital control commands from controller, and drives external relays, solenoid valves and other field actuators. It provides isolation between control system and field load circuit. It has overcurrent protection function for output channels.

Category:

Description

Emerson 1C31150G01

Technical Specifications: Power supply:24VDC. Isolation voltage:1500VAC. Operating temperature:0℃~60℃. Storage temperature:-40℃~85℃. Humidity:5%~95% non-condensing.

Functional Features: Each output channel has independent overcurrent protection. LED status indicator shows channel output state. Galvanic isolation between system side and field load side. Support matched I/O card hot swap. Screw terminal design for field load wiring.

Application Scenarios: Pump start-stop control, on-off valve drive, fan interlock control, chemical plant solenoid valve control, power plant auxiliary equipment relay control.

Performance Parameters: Maximum output load per channel: 1A. Response time: less than 2ms. Vibration resistance:10~150Hz,0.5g. Shock resistance:10g,11ms. MTBF:195000 hours.

Material Composition: Shell: UL94-V0 flame retardant plastic. Terminal: nickel-plated brass. PCB: FR4 glass epoxy substrate. Protection components soldered on circuit board. Mounting clip: stainless steel.

Structural Features: 35mm DIN rail snap installation. Front panel with LED indicators and channel marking. Upper card slot for digital output card. Screw terminals arranged on front lower part. Anti-misplug structure.

Working Principle: Ovation controller sends digital output command to digital output card. The card controls the circuit on terminal base. The terminal base outputs switch signal to drive field actuators. The isolation circuit separates high energy field load circuit and low voltage control circuit.

Installation Requirements: Install on 35mm DIN rail. Reserve 25mm heat dissipation space. Field load cable and control signal cable separate wiring. Terminal screw torque 0.6~0.8N·m. Cut off power before wiring operation.

Precautions for Use: Do not exceed rated load current of each channel. Wear anti-static wristband when touching circuit. Check terminal tightness regularly. Stop using when shell appears burning trace.