Honeywell MC-GOAX02 51304638-175

Product Introduction MC-GOAX02 51304638-175 is an 8-channel analog output card for the Honeywell Experion PKS C-series, part number 51304638-175. The card converts controller outputs into 4 to 20 mA signals driving field control valves, with channel isolation and fault diagnosis. It is inserted in the C200/C300 controller I/O rack for petrochemical, refining, and oil/gas DCS.

Category:

Description

Honeywell MC-GOAX02 51304638-175

Technical Specifications

  • Product type: Analog output card
  • Channels: 8 AO
  • Output: 4 to 20 mA
  • Accuracy: 0.1 % FS
  • Load: Max 750 Ω
  • Supply: Rack backplane
  • Isolation: Channel isolation
  • Temperature: -20 °C to +60 °C
  • Storage: -40 °C to +85 °C
  • Humidity: 5 % to 95 %, non-condensing
  • Protection: IP20
  • Installation: Card socket
  • Certifications: UL, CE

Functional Features

  • 8-channel 4 to 20 mA output
  • 0.1 % high precision
  • Independent channel optical isolation
  • Output loop wire-break diagnosis
  • Front panel LEDs per channel
  • Fail-safe output mode (hold or drive to zero)
  • Experion C-series bus communication
  • Electronic channel configuration
  • Online replacement
  • Industrial wide-temperature design

Application Scenarios

  • Refinery control valve output
  • Petrochemical DCS analog output
  • Oil/gas platform control valve signal
  • Chemical reactor control output
  • Experion PKS AO cards

Materials and Construction

  • Housing: Flame-retardant engineering plastic
  • PCB: FR4 board with conformal coating
  • Core: 8-channel DAC, V/I circuit
  • Connector: C-series dedicated backplane
  • Terminals: FTA field terminal board
  • Passive components: Precision resistors, TVS

Structural Features

  • Narrow card in C-series I/O socket
  • Front panel channel LEDs
  • Right-side FTA field terminal board
  • Independent channel isolation
  • Removable terminal block
  • Card locking mechanism

Working Principle The controller sends setpoints over C-series bus; the DAC converts to voltage and the V/I circuit produces 4 to 20 mA to the valve. Output loop monitoring detects wire-break. On failure the card drives a preset fail-safe value. LEDs indicate channel status.

Installation Requirements

  • Insert I/O socket with power off
  • Connect FTA terminals per drawing
  • Shielded twisted pair output
  • Do not short output
  • Rack grounding
  • Temperature -20 °C to +60 °C
  • Configure output range in engineering station

Precautions

  • Confirm system support before online replacement
  • Do not short output
  • Load must not exceed 750 Ω
  • Wear ESD wrist strap
  • Store spares in anti-static moisture-proof packaging
  • Verify output from software after replacement