Honeywell MC-41110400

Product Introduction MC-41110400 is a digital input card for the Honeywell TPS system. The card acquires field 24 V switch signals over the TPS bus to the control station, with channel isolation and fault diagnosis. It is a card in the TPS rack I/O slot for refining, petrochemical, and chemical DCS switch signal acquisition.

Category:

Description

Honeywell MC-41110400

Technical Specifications

  • Product type: Digital input card
  • Channels: Multi-channel DI
  • Inputs: DC24 V dry contact / PNP
  • Input current: About 5 mA per channel
  • Isolation: Channel group isolation
  • Supply: Rack backplane
  • Response: 5 ms
  • Temperature: 0 °C to +60 °C
  • Storage: -20 °C to +70 °C
  • Humidity: 5 % to 95 %, non-condensing
  • Protection: IP20
  • Installation: Eurocard plug-in

Functional Features

  • Multi-channel DC24 V digital input
  • Dry contact and PNP proximity switch
  • Channel wire-break diagnosis
  • Front panel LEDs per channel
  • Channel group optical isolation
  • TPS bus communication
  • Input filter time software configurable
  • Non-volatile channel configuration
  • Industrial-grade components
  • Continuous operation

Application Scenarios

  • Refinery field switch acquisition
  • Petrochemical valve position feedback
  • Chemical DCS digital input
  • Plant switch signal monitoring
  • TPS DI cards

Materials and Construction

  • Front panel: Metal panel
  • PCB: FR4 board with conformal coating
  • Input: Optocouplers, current-limiting resistors
  • Connector: Gold-plated Eurocard
  • Terminals: Screw-fastened terminals
  • Passive components: TVS, metal film resistors

Structural Features

  • Eurocard plug-in in TPS rack I/O slot
  • Front panel channel LEDs and terminals
  • Channel group isolation
  • Card locking mechanism
  • Removable terminal block
  • Metal panel shielding

Working Principle Field DC24 V signals enter terminals; after current-limiting, optocouplers convert to digital logic; filtering de-bounces before uploading over TPS bus to control station. Diagnostics monitor loop current to identify wire-break. LEDs indicate channel status.

Installation Requirements

  • Insert I/O slot with power off
  • Shielded twisted pair, single-point ground
  • Route signal and power cables separately
  • Rack grounding
  • Temperature 0 °C to +60 °C
  • Configure channel filter in software

Precautions

  • Do not hot-swap online
  • Input must not exceed DC30 V
  • Wear ESD wrist strap
  • Verify channels from software after replacement
  • Store spares in anti-static moisture-proof packaging
  • Periodically tighten terminals