INCA Chloride SG-1124-4
Technical Specifications
- Product type: Switch mode rectifier / battery charger
- Input: AC110 V / AC230 V
- Output: DC24 V
- Rated current: Corresponding to model rating
- Battery: Lead acid 24 V
- Charge modes: Float charge, boost charge
- Efficiency: High frequency switching
- Protection: Over voltage, over current, short circuit
- Operating temperature: 0 °C to +50 °C
- Storage temperature: -20 °C to +70 °C
- Humidity: 5 % to 95 %, non-condensing
- Protection: IP20
- Installation: Rack / panel
- LEDs: AC input, DC output, battery fault
Functional Features
- Switch mode DC24 V regulated output
- Automatic battery float and boost charge
- LED status indication for AC, DC, and fault
- Overvoltage and overcurrent protection
- Hot swap rectifier module
- Low ripple DC output
- Current sharing for parallel redundancy
- Battery reverse polarity protection
- Industrial continuous operation
- Front panel test pushbutton
Application Scenarios
- Substation DC control supply
- Industrial battery charger panel
- Emergency lighting DC distribution
- Telecommunication standby battery
- Plant control power with battery backup
Materials and Construction
- Housing: Coated metal
- PCB: FR4
- Power semiconductors: IGBT / MOSFET
- Capacitors: Electrolytic
- Heat sink: Aluminum
- Connector: Rack backplane connector
Structural Features
- Rack plug-in rectifier module
- Front panel LEDs and test button
- Rear backplane connector
- Internal EMI filter, rectifier, switching stage
- Heat sink on power devices
- Front handle for insertion and extraction
Working Principle AC input is rectified and switched at high frequency. Transformer isolates and steps down; secondary rectifier produces DC24 V. Battery connects across output. The charger maintains float voltage; when AC fails, battery discharges to load. Monitoring circuits protect output and battery.
Installation Requirements
- Insert into DC panel rack
- Select AC input voltage
- Connect battery with correct polarity
- Connect DC load bus
- Temperature 0 °C to +50 °C
- Grounding
- Verify float voltage after power-up
- Redundant rectifiers share current
Precautions
- Battery polarity must not be reversed
- Do not short DC output
- Battery ventilation required
- Replace electrolytic capacitors at end of life
- Store spares in dry environment
- Periodically measure battery voltage
- Disconnect AC before service