Description
Yokogawa KS1-10-B
Technical Specifications
- Product type: Signal isolator
- Input: 4 to 20 mA
- Output: 4 to 20 mA
- Supply: DC24 V
- Isolation: 1500 VAC three-way
- Accuracy: ±0.1 % FS
- Response time: 100 ms
- Temperature: 0 °C to +55 °C
- Storage: -20 °C to +70 °C
- Humidity: 5 % to 90 %, non-condensing
- Protection: IP20
- Installation: DIN rail
- Channels: 1 channel isolation
Functional Features
- 4 to 20 mA one-in one-out isolation
- Three-way 1500 VAC isolation blocking ground loops
- ±0.1 % FS accuracy
- Loop-powered or external powered options
- Front panel LEDs for power and signal
- Compact DIN rail mounting
- Industrial-grade long-term stability
- Isolation protects downstream equipment
- Channel fault diagnostic output
- Withstands strong industrial EMI
Application Scenarios
- Petrochemical process control signal isolation
- Chemical DCS analog signal distribution
- Power plant transmitter signal isolation
- Water treatment 4 to 20 mA signal transfer
- General industrial process signal isolation
Materials and Construction
- Housing: Flame-retardant engineering plastic
- PCB: FR4 board
- Core: Isolation amplifier, DC/DC supply
- Passive components: Metal film resistors, ceramic capacitors
- Terminals: Screw-fastened terminals
- Mounting clip: 35 mm DIN rail clip
Structural Features
- Narrow DIN rail plastic housing
- Top input terminals, bottom output terminals
- Side supply terminals
- Internal isolation transformer and amplifier
- Fanless natural convection
- Compact width saving cabinet space
Working Principle Field 4 to 20 mA enters input terminals; V/I conversion feeds an isolation transformer that transfers the signal to the output side. The transformer provides 1500 VAC three-way isolation; the output side reconstructs a 4 to 20 mA current to the PLC. DC24 V supply feeds a DC/DC converter powering both sides. LEDs indicate power and signal.
Installation Requirements
- Snap-mount on 35 mm DIN rail
- Connect input/output terminals per markings
- Connect DC24 V supply
- Use shielded twisted pair signal wires
- Cabinet temperature 0 °C to +55 °C
- Verify signal direction after power-up
Precautions
- Never reverse input and output
- Do not overload
- Store spares in dry environment
- Periodically check output accuracy
- Disconnect power before service
- Route signal wires separately from power cables