ABB PL810P 3BDH000311R0101

Product Overview
The ABB PL810P is a Power Link Module used in ABB industrial control and fieldbus infrastructure. It supplies power to a PROFIBUS PA segment and links the PROFIBUS PA fieldbus to an ABB head station or linking device. The module enables PROFIBUS PA devices to receive bus power and communicate through a 31.25 kbit/s PA segment. It is designed for process automation, field instrument integration, and distributed I/O applications where PROFIBUS PA is used.

Category:

Description

ABB PL810P 3BDH000311R0101

Technical Specifications

  • Brand: ABB
  • Product Type: Power Link Module for PROFIBUS PA
  • Order Number: 3BDH000311R0101
  • Nominal Supply Voltage: 20 to 35 V DC
  • PROFIBUS PA Segment Voltage: 24 to 26 V nominal
  • PROFIBUS PA Segment Current: Up to 400 mA
  • PROFIBUS PA Baud Rate: 31.25 kbit/s
  • Fieldbus Standard: IEC 61158-2, EN 50170/2
  • Protocol Support: PROFIBUS DP V1 upstream communication
  • PROFIBUS PA Devices per Segment: Up to 32 devices
  • Terminator Impedance: 100 Ohm integrated
  • Galvanic Isolation: Functional isolation between channel, PROFIBUS DP, PROFIBUS PA, and power sections
  • Designed Isolation Voltage: 50 V AC
  • EMC Compliance: NAMUR NE 21
  • ATEX Approval: TÜV 02 ATEX 1886 X
  • Ex Rating: II 3 G EEx nA II T4
  • Installation Area: Zone 2 capable depending on system configuration

Functional Features

  • PROFIBUS PA Power Supply: Provides regulated power to PROFIBUS PA field devices.
  • Linking Function: Connects PROFIBUS PA to a PROFIBUS DP or head station network.
  • No Programming Required: Operates as a fieldbus infrastructure module without user program download.
  • Integrated Terminator: Includes a 100 Ohm terminator for segment termination.
  • Galvanic Isolation: Separates fieldbus, power, and channel circuits to reduce interference.
  • Zone 2 Capability: Suitable for use in Zone 2 hazardous areas when approved by the system design.
  • Removable Terminals: Allows convenient wiring and maintenance.

Application Scenarios

  • Process automation systems
  • PROFIBUS PA field instrument networks
  • Chemical and pharmaceutical plants
  • Oil and gas field monitoring
  • Power plant instrumentation
  • Water and wastewater treatment
  • Distributed control system fieldbus expansion
  • Legacy ABB OCS and DCS fieldbus maintenance

Performance Parameters

  • PA Segment Speed: 31.25 kbit/s
  • PA Device Capacity: Up to 32 devices per segment
  • Supply Range: 20 to 35 V DC
  • PA Output Current: Up to 400 mA
  • Isolation Level: Functional isolation with 50 V AC designed isolation voltage
  • EMC Robustness: Designed according to NAMUR NE 21

Material Composition

  • Housing: Industrial plastic enclosure
  • Terminal Blocks: Removable screw or spring terminals
  • PCB Assembly: Power regulation, fieldbus interface, and isolation circuits
  • Connectors: Fieldbus terminals and head station connection terminals
  • Indicators: Status LEDs for power and communication monitoring

Structural Features

  • Modular Design: Mounts as part of an ABB fieldbus or control system assembly.
  • Removable Wiring Terminals: Simplifies installation and replacement.
  • Integrated Bus Terminator: Reduces external wiring for segment termination.
  • Compact Industrial Form Factor: Fits standard control panel or fieldbus mounting arrangements.
  • Clear Terminal Marking: Supports correct PA bus and power wiring.

Working Principle
The PL810P receives 20 to 35 V DC supply power and conditions it for the PROFIBUS PA segment. It provides up to 400 mA to connected PA field devices while maintaining the 31.25 kbit/s communication level defined by IEC 61158-2. Data from PA devices is passed through the linking device to the PROFIBUS DP or head station network. The module does not execute user logic; it acts as a physical layer power and communication link between the PA segment and the higher-level bus.

Installation Requirements

  • Install according to the ABB PL810P installation manual.
  • Verify compatibility with the connected head station or linking device.
  • Supply 20 to 35 V DC within the specified tolerance.
  • Connect the PROFIBUS PA segment to the correct fieldbus terminals.
  • Wire the link to the head station using the specified terminals.
  • Ensure proper grounding and shielding for PROFIBUS PA cabling.
  • Observe Zone 2 installation rules if used in hazardous areas.
  • Confirm the number of connected PA devices does not exceed segment current limits.

Precautions for Use

  • Do not exceed the 400 mA PROFIBUS PA segment current limit.
  • Verify that the head station or linking device supports the PL810P.
  • Do not use the module as a general-purpose PLC CPU.
  • Maintain correct polarity for supply and bus connections.
  • Confirm ATEX and Zone 2 requirements with the system integrator.
  • Use shielded PROFIBUS PA cable and proper termination.
  • For exact environmental ratings, terminal assignments, and certification limits, refer to the official ABB PL810P documentation.