Description
Eaton XV-232-57BAS-1-13-1
Technical Specifications: Display size:5.7 inch TFT color display Touch type:4-wire resistive touch screen Resolution:640 × 480 pixels Processor:400MHz RISC CPU RAM:256MB Flash memory:256MB Communication:Ethernet, RS232, RS485, optional CAN/Profibus Power supply:24VDC Front panel protection:IP65 Operating temperature:0℃ to 55℃ Storage temperature:-20℃ to 70℃ Humidity:10%~90%, non-condensing
Functional Features: Combined HMI visualization and CODESYS embedded PLC complying with IEC61131-3. Built-in protocol gateway function for data conversion between different field buses. Real-time trend curve display and historical alarm logging. Recipe storage function for batch production parameter switching. Multi-level user access password management. SD card support for program backup, restore and log export. Hardware watchdog function for automatic fault recovery. Galileo software for HMI screen project programming.
Application Scenarios: Packaging machinery, textile equipment, small injection molding machines, conveyor control cabinets, water treatment local control panels, printing auxiliary machines.
Performance Parameters: Minimum PLC scan cycle 1ms. Screen refresh cycle 100ms. Nonvolatile data retention time reaches 10 years. Resistive touch operation service life over 1 million touches.
Material Composition: Front panel: Reinforced flame retardant plastic with rubber sealing gasket. PCB: FR4 high reliability industrial printed circuit board. Display module: TFT LCD with LED backlight. Touch sensor: 4-wire resistive film. Rear casing: Flame retardant ABS plastic. Mounting clips: Zinc coated spring steel.
Structural Features: Panel cutout mounting form factor. Sealed front panel design for IP65 dust and splash protection. Rear side contains power terminal block and multiple communication connectors. LED power and fault status indicators. Spring steel mounting clips for fast locking and installation. Internal separation layout of power circuit and signal circuit.
Working Principle: 24VDC power supplies the embedded RISC processor and display module. The processor executes HMI graphical program and PLC logic simultaneously. Ethernet and serial communication ports exchange data with external PLC and field instruments. Resistive touch controller converts touch operation into digital command and transmits to processor. TFT screen displays process variables, setpoint values and alarm information. SD card stores backup project files and historical operation logs. Hardware watchdog monitors system running state continuously.
Installation Requirements: Mount through control cabinet panel cutout. Reserve 20mm rear clearance for heat dissipation. Tighten mounting clips evenly to avoid gasket deformation. Connect protective earth wire reliably. Separate power wiring and signal wiring in different cable channels. Avoid installation near high-power contactors and frequency converters.
Usage Notes: Use isolated 24VDC SELV power supply only. Do not use sharp hard objects to press touch screen surface. Backup project data before firmware modification. Cut power before connecting or disconnecting field cables. Clean front panel with soft neutral cloth only. Inspect sealing gasket condition after panel disassembly.