GE IC695CHS007

Product Overview

The IC695CHS007 is a 7-slot universal backplane for the GE PACSystems RX3i series, designed to accommodate CPU, power supply, I/O, and communication modules. It provides the electrical and mechanical connections for all modules, ensuring reliable communication and power distribution across the PLC system

Category: SKU: GE IC695CHS007

Description

GE IC695CHS007

Technical Specifications

Parameter Specification
Slot Count 7 slots (universal)
Module Compatibility RX3i CPU, power supply, I/O, communication, and specialty modules
Power Distribution Provides 5V DC and 24V DC to modules via backplane buses
Communication Supports high-speed VME64 backplane bus for module-to-module communication
Operating Temperature 0°C to 60°C
Humidity 5% to 95% (non-condensing)
Dimensions 34mm × 145mm × 140mm (approx.)
Mounting DIN rail or panel mounting

Functional Characteristics

  • Universal Slot Design: Any module can be installed in any slot, providing flexibility in system configuration.
  • High-Speed Bus: Supports VME64 standards for fast data transfer between modules.
  • Power Management: Distributes regulated power to all modules while including current-limiting protection.
  • Hot-Swap Support: Allows module replacement without system shutdown (if using hot-swappable power supplies).

Application Scenarios

  • Main PLC Rack: Typically used as the primary rack for CPU and critical I/O modules in medium-sized systems.
  • Expansion Racks: Can be used in multi-rack configurations for larger systems (via expansion modules).
  • Distributed Control: Serves as a local rack in distributed control systems (DCS).
  • Test Benches: Used in testing environments for modular system prototyping.

Installation & Usage Notes

  • Ensure proper grounding of the backplane to minimize noise and ensure reliable operation.
  • Use appropriate end plates to protect exposed slots.
  • The backplane does not include a power supply; a compatible power module (e.g., IC694PWR330) must be installed.
  • Verify module compatibility with the backplane slot count before installation.