Product Introduction This high-temperature UV flame detector is rated for installation in high-ambient-temperature locations near furnace walls and hot combustion zones. Its heat-resistant housing and internal components withstand sustained 125 °C ambient temperatures, providing reliable flame detection for high-temperature industrial furnace applications.

Category:

Description

Honeywell C7035A1080

Technical Specifications

  • Detection band: 190–270 nm ultraviolet
  • Detection response time: ≤0.2 seconds
  • Output signal: SPDT dry contact, contact rating 2 A / 220 V AC
  • Supply voltage: 120 V AC 50/60 Hz
  • Operating temperature: -40 °C to +125 °C sustained
  • Detection angle: 60° conical field of view
  • Protection rating: IP65

Functional Features High-temperature rated components, withstand sustained 125 °C ambient without signal drift. Heat-dissipating finned housing, draws heat away from internal sensor components. Ceramic insulated internal wiring, rated for high-temperature operation. Compatible with all Honeywell RM7800 flame safeguard controls. Internal shutter protects the window in high-dust hot furnace environments. Stable UV sensitivity at elevated temperatures, no drift in detection threshold.

Application Scenarios Flame detection near furnace walls in high-temperature metallurgical furnaces Sustained high-ambient-temperature boiler burner monitoring Refinery heater flameout protection Spare part replacement for standard UV detectors failing in high-temperature locations

Performance Parameters

  • Detection range: Stable detection of main flame within 6 meters
  • Sensitivity drift over 0–125 °C range: ≤2%
  • Ambient light rejection: 15,000 lux visible light without false trigger
  • Heat dissipation fin area: 2 times standard C7035 housing
  • Mounting thread: 1 inch NPT

Material Composition High-temperature cast aluminum housing with cooling fins Ceramic insulated internal wiring High-temperature UV photosensitive tube Thick quartz glass window Stainless steel shutter mechanism High-temperature ceramic cable gland

Structural Features Finned cylindrical cast aluminum housing, designed for heat dissipation. Front thick quartz detection window. Rear high-temperature ceramic cable gland. 1 inch NPT mounting thread. Internal wiring uses ceramic standoffs instead of plastic parts.

Working Principle Flame ultraviolet radiation passes through the quartz window to the high-temperature rated UV photosensitive tube. The tube maintains stable conductivity across the full 0–125 °C temperature range, triggering the internal relay to output a flame present signal on UV exposure. The finned housing dissipates ambient heat away from the internal sensor, preventing component overheating. On flameout, UV signal disappears, the relay opens to trigger safety shutdown.

Installation Requirements Mount the detector with the finned side exposed to ambient air, do not enclose the fins. Maintain minimum 5 cm clearance around the fins for air circulation. Connect supply and output wiring using high-temperature rated cable. Verify detection stability during full operating temperature conditions.

Usage Notes Never paint the cooling fins, paint blocks heat dissipation and causes internal overheating. Do not mount the detector in a stagnant hot air pocket, this defeats fin cooling. Standard leads cannot be used at sustained temperatures above 100 °C, use high-temperature wire. Inspect internal ceramic standoffs annually for cracking from thermal cycling.