Description
ICS Triplex P153DL002
Technical Specifications
- Product type: TMR digital input module
- Channels: Multi-channel DI
- Input signal: DC24 V dry contact
- Redundancy: TMR 2-out-of-3 voting
- Isolation: Channel group isolation
- Safety level: SIL3
- Supply: Rack backplane
- Operating temperature: 0 °C to +60 °C
- Storage temperature: -20 °C to +70 °C
- Humidity: 5 % to 95 %, non-condensing
- Protection: IP20
- Installation: Eurocard plug-in
- Diagnosis: Channel wire-break and short-circuit
Functional Features
- TMR 2-out-of-3 voting digital input
- SIL3 safety integrity
- Channel wire-break and short-circuit diagnosis
- Single channel fault tolerance
- Front panel LEDs per channel
- Channel group optical isolation
- Backplane bus isolated from field
- Event sequence of recording (SOE)
- Industrial continuous operation
- Suited to SIS critical applications
Application Scenarios
- Petrochemical SIS safety switch input
- Offshore ESD emergency stop signals
- Chemical unit emergency shutdown
- Power plant boiler FSSS signals
- Pharmaceutical explosion-proof safety door monitoring
Materials and Construction
- Front panel: Metal panel
- PCB: FR4 board with conformal coating
- Input devices: Optocouplers
- Connector: Gold-plated Eurocard
- Terminals: Screw-fastened terminals
- Passive components: TVS, resistors
Structural Features
- Eurocard plug-in in TMR rack
- Front panel LEDs and terminals
- Three independent redundant circuit paths
- Card locking mechanism
- Metal shielding panel
- Removable terminal block
Working Principle Field switch signals feed three independent input circuits simultaneously. The 2-out-of-3 voting circuit compares the three results; if one path disagrees with the other two, the channel is marked faulty but the system continues on the majority result. Diagnosis circuits identify wire-break and short-circuit. LEDs indicate channel status.
Installation Requirements
- Insert TMR rack slot with power off
- Shielded twisted pair field signal wires
- Separate signal and power cables
- Rack grounding
- Temperature 0 °C to +60 °C
- Configure channels in engineering software
- TMR redundancy pairing
Precautions
- Do not hot-swap online
- Input must not exceed DC30 V
- Wear ESD wrist strap
- Verify channels from software after replacement
- Store spares in anti-static moisture-proof packaging
- Periodically tighten terminals