ICS Triplex P153DL002

Product Introduction P153DL002 is a digital input module for the ICS Triplex (Rockwell) TMR triple modular redundancy system. The card acquires field safety switch signals with 2-out-of-3 voting architecture; a single channel fault does not affect safety logic. It is a card inserted in the TMR rack for SIS safety interlock systems in petrochemical, oil and gas, and chemical plants.

Category:

Description

ICS Triplex P153DL002

Technical Specifications

  • Product type: TMR digital input module
  • Channels: Multi-channel DI
  • Input signal: DC24 V dry contact
  • Redundancy: TMR 2-out-of-3 voting
  • Isolation: Channel group isolation
  • Safety level: SIL3
  • Supply: Rack backplane
  • Operating temperature: 0 °C to +60 °C
  • Storage temperature: -20 °C to +70 °C
  • Humidity: 5 % to 95 %, non-condensing
  • Protection: IP20
  • Installation: Eurocard plug-in
  • Diagnosis: Channel wire-break and short-circuit

Functional Features

  • TMR 2-out-of-3 voting digital input
  • SIL3 safety integrity
  • Channel wire-break and short-circuit diagnosis
  • Single channel fault tolerance
  • Front panel LEDs per channel
  • Channel group optical isolation
  • Backplane bus isolated from field
  • Event sequence of recording (SOE)
  • Industrial continuous operation
  • Suited to SIS critical applications

Application Scenarios

  • Petrochemical SIS safety switch input
  • Offshore ESD emergency stop signals
  • Chemical unit emergency shutdown
  • Power plant boiler FSSS signals
  • Pharmaceutical explosion-proof safety door monitoring

Materials and Construction

  • Front panel: Metal panel
  • PCB: FR4 board with conformal coating
  • Input devices: Optocouplers
  • Connector: Gold-plated Eurocard
  • Terminals: Screw-fastened terminals
  • Passive components: TVS, resistors

Structural Features

  • Eurocard plug-in in TMR rack
  • Front panel LEDs and terminals
  • Three independent redundant circuit paths
  • Card locking mechanism
  • Metal shielding panel
  • Removable terminal block

Working Principle Field switch signals feed three independent input circuits simultaneously. The 2-out-of-3 voting circuit compares the three results; if one path disagrees with the other two, the channel is marked faulty but the system continues on the majority result. Diagnosis circuits identify wire-break and short-circuit. LEDs indicate channel status.

Installation Requirements

  • Insert TMR rack slot with power off
  • Shielded twisted pair field signal wires
  • Separate signal and power cables
  • Rack grounding
  • Temperature 0 °C to +60 °C
  • Configure channels in engineering software
  • TMR redundancy pairing

Precautions

  • Do not hot-swap online
  • Input must not exceed DC30 V
  • Wear ESD wrist strap
  • Verify channels from software after replacement
  • Store spares in anti-static moisture-proof packaging