Description
ICS Triplex T9432
Technical Specifications
- Input Channels: 16 isolated analogue input channels
- Input Voltage Range: 18 to 32 VDC
- Maximum Current: 260 milliamperes
- Power Consumption: 4.0 Watts
- Heat Dissipation: 4.0 Watts
- Redundancy Options: Simplex, Dual, or Triple configurations
- Scan Time Simplex: 1.170 milliseconds
- Scan Time Dual: 1.965 milliseconds
- Scan Time Triple: 2.656 milliseconds
- Weight: 340 grams
- Operating Temperature: Minus 40 degrees Celsius to plus 70 degrees Celsius
- Relative Humidity: 10 to 95 percent non-condensing
- Resolution: 16-bit
- Input Range: Minus 10 V to plus 10 V
Functional Features
- Comprehensive galvanic and photoelectric isolation on each channel containing destructive field electrical spikes
- Scalable across Simplex, Dual Redundant, or Triple Modular Redundant safety voting matrices
- 16-bit resolution for accurate measurement of analogue signals
- Sampling rate of 1000 samples per second
- Wide diagnostic coverage including monitoring of power supply, channel input, and internal circuits
- Configuration through ICS Triplex Triconex Engineering Workstation software
Application Scenarios
- Power generation monitoring and control
- Oil and gas process variable tracking
- Manufacturing precision control
- Chemical processing continuous monitoring
- Pharmaceutical process control
Performance Parameters
- 1.170 millisecond scan time in Simplex configuration for fast data processing
- 16-bit resolution capturing precise signal details
- 1000 samples per second sampling rate for dynamic signal capture
- Elimination of false process trips through redundant voting matrices
Material Composition and Structure
- Compact lightweight industrial chassis
- Conformal coated circuit boards
- Isolated input circuitry with galvanic barriers
- High-density connector interfaces
- Status indicators for module health
Working Principle The module converts analogue field signals into digital values through 16-bit analog-to-digital converters. Each channel operates independently with full isolation from field common. In redundant configurations, multiple modules process the same inputs and vote on the correct value, eliminating false trips from single-channel failures. Diagnostics continuously monitor power, input signals, and internal circuitry.
Installation Requirements
- Install in AADvance chassis with proper slot alignment
- Connect field signals within minus 10 V to plus 10 V range
- Use shielded cables for analogue inputs
- Configure redundancy level per application safety requirements
- Ensure proper grounding of field common
Operating Precautions
- Verify input signals remain within specified voltage range
- Monitor scan times to ensure deterministic performance
- Check diagnostic status regularly for channel health
- Replace modules showing persistent fault indications
- Maintain configuration backups before modifications