GE IC695ALG708

Product Overview

The IC695ALG708 is a high-performance analog output module for the RX3i series, providing eight isolated output channels with programmable voltage and current ranges. It is designed for applications requiring precise control of actuators, valves, and drives, such as motion control, process automation, and test equipmen

Category: SKU: GE IC695ALG708

Description

GE IC695ALG708

Technical Specifications

Parameter Specification
Output Channels 8 points (galvanically isolated)
Output Signal Types Voltage: ±10V, ±5V, 0-10V, 0-5V Current: 0-20mA, 4-20mA
Resolution 16-bit
Settling Time <5ms (to ±0.1% of full scale)
Isolation Voltage 500V AC continuous between channels and backplane
Operating Temperature -40°C to 70°C
Humidity 5% to 95% (non-condensing)
Backboard Current Draw 320mA at 5V DC
Terminal Type Removable terminal block
Indicators 8 individual LEDs for channel status

Functional Characteristics

  • High-Speed Output: Fast settling times enable precise control of high-speed actuators and drives.
  • Universal Output: Supports both voltage and current outputs, reducing the need for external converters.
  • Galvanic Isolation: Each output is isolated to prevent ground loops and ensure signal integrity.
  • Software Configurability: Output ranges, scaling, and alarm thresholds are programmable via GE software.

Application Scenarios

  • Motion Control: Controlling servo drives and positioners in robotic systems.
  • Process Automation: Regulating valves, pumps, and variable frequency drives (VFDs).
  • Test & Measurement: Generating analog signals for sensor calibration and equipment testing.
  • Building Automation: Controlling damper actuators and lighting intensity systems.

Installation & Usage Notes

  • Use shielded cables for output wiring to minimize noise in sensitive applications.
  • The module supports hot swapping for maintenance without system interruption.
  • Ensure load impedance matches the selected output range to avoid damage.
  • Configure output scaling and limits in the PLC program to match field device requirements.